Six zero-days found in Danfoss supermarket fridge controller allow remote takeover
- Severity
- Critical
- Sources
- 1
What happened
Midnight Blue (Carlo Meijer) disclosed six pre-authentication RCE flaws in the Danfoss AK-SM800A supermarket controller, all stack-based buffer overflows from unsafe strcpy use, affecting all firmware up to and including 5.3.2. No CVE IDs have been assigned, and details are withheld during coordinated disclosure. Strict mode, the default from 4.0, reduces the unauthenticated web attack surface, but an overflow in smfcgiapp still works on the latest firmware with strict mode on. The device lacks i.MX6 secure boot, so root access allows persistent implants or wiping. Defenders should find all exposed controllers, including those behind integrator 4G modems, and move remote access behind a VPN, private APN or strict IP allow list, noting CERT-FR says allow lists are only a short-term fix.
For security analysts · Written by AI from 1 source · Wrong?
What to do
- Find every exposed Danfoss and Copeland controller, including those behind integrator 4G modems.
- Move remote access to these controllers behind a VPN, a private APN or a strict IP allow list.
- Treat a strict IP allow list as a short-term measure only, as CERT-FR advises.
Written by AI from the sources, checked against them
Full story timeline · 1 update
Who reported · 1 outlet
Who and what is in it
Companies
Products
Government agencies